ICS Logo Supplying & Supporting VESDA detection to the UK Trade
Home About Us Contact Us Account  
   
 
           
ICS Suppliers of VESDA detection to the Trade.
     
  LaserSCANNER  
  LaserPLUS  
  LaserCOMPACT  
  LaserFOCUS 250  
  LaserFOCUS 500  
  Remote Display  
  Programmers  
  19" Rack  
  Interfaces  
  Network Cards  
  Multi Function Cards  
  Power Supplies  
     
     

 

LaserSCANNER Specifications

Supply Voltage: 18 to 30VDC

Power Consumption @ 24VDC: No Display or Programmer

 
Aspirator @ 3000rpm
Aspirator @ 4200rpm
 
Quiescent
With Alarm
Quiescent
With Alarm
Power
5.8W
7.4W
9.6W
11.28W
Current
240mA
310mA
400mA
470mA

Dimensions (WHD):
350mm x 225mm x 125mm (13.8in x 8.9in x 4.9in)

Weight: 4.0kg (9lbs) including Display and Programmer modules

Operating Conditions:
Detector Ambient: 0°C to 39°C (32° to 103°F)
Sampled Air: -20° to 60°C (-4° to 140°F)
Humidity: 10-95% RH, non-condensing

Please consult ICS for operation outside these parameters or where sampled air is continually above 0.05% obs/m (0.015% obs/ft) under normal operating conditions.

Sampling Network:
Aggregate pipe length: 200m (650ft)
Pipe Modelling Design Tool: ASPIRE™

Pipe Size: Minimum flow per pipe I5 litres/min.
External Diameter 25mm (1in)
Internal Diameter I5-2I mm (9/16in - 7/8in)

Programmable Relays: 7 or 12 Relays option Contacts rated 2A @ 30VDC
Default: 7 Relays: NO/NC contacts Alert, Action, Fire 1, Fire 2, Maintenance, Urgent Fault & Isolate
Default: 12 Relays: 10 x NO, 2 x NO/NC contacts Alert, Action, Fire 1, Fire 2, Maintenance, Urgent Fault & Isolate, First Alarm Sector 1 to 4 and Scan

IP Rating: IP30

Cable Access:
8 x 25 mm (1 in) knockouts in various positions

Cable Termination:
Screw terminals 0.2-2.5sq mm (30-12 A.G.)

Sensitivity Range:
0.005 to 20% obs/m (0.0015 to 6% obs/ft)

Alarm Threshold Setting Range:
Alert: 0.005 - 1.990% obs/m (0.0015 - 0.62 I 8% obs/ft)
Action: 0.010 - 1.995% obs/m (0.003 I - 0.6234% obs/ft)
Fire 1: 0.015 - 2.00% obs/m (0.0046 - 0.625% obs/ft)
Fire 2: 0.020 - 20.00% obs/m (0.0062 - 6.25% obs/ft)*
*Limited to 12% obs/m (4% obs/ft) in UL mode

Software Features:
Event Log: Up to 18,000 events stored on FIFO basis.
AutoLearn: Minimum I 5 minutes, maximum 15 days.
Recommended minimum period 1 day. During AutoLearn thresholds are NOT changed from pre-set values.
Referencing: Compensation for external ambient conditions
Four Alarm Levels (per sector pipe):
Alert, Action, Fire 1 & Fire 2
Two Fault Warning Levels: Maintenance and Major fault
Software Programmable Relays: 7 or 12
Maintenance Aids: Filter & Flow monitoring. Event reporting via VESDAnet or Event Log.
Adaptive Scan Threshold: Detector selects the appropriate scan threshold automatically

 
Download Data Sheet