VESDA Programmer Specification
Screen Display Size:
70 mm x 37 mm (2.75 in x 1.45 in)
Full Graphic display
Large characters
8 lines, 21 characters per line
Adjustable backlit screen with contrast control
Inactivity Time Out:
10 minutes (Defaults to log on screen)
Beeps at 1 minute and then 15 seconds before Logoff
Push Button Keys:
2 Rows x 4 keys, each 19 mm x 12 mm (0.75 in x 0.50 in)
Security Access:
3 characters User lD
4 digit Personal Identification Number (PIN) per User
Number of User Levels:
10 USR
3 ADM
1 DST
Default ID:
USR = User (Operator level)
ADM = Administrator (Access most functions)
DST = VESDA Distributor (Access all functions)
Operating Conditions:
Tested to: -10°C–55°C (14°F–131°F)
Recommended Detector Ambient:
0°C–39°C (32°–103°F)
Humidity:
10%–95% RH, non-condensing
System Functions Accessed:
Status of software version
Descriptive Alarms & Faults
Smoke & Flow readings
Push-Button lockout
Display name (21 chars)
Alarm Thresholds (Alert, Action, Fire 1 & Fire 2)
Alarms delays (0–60 seconds)
Day/Night/Weekend/Holiday Options
Event Log (up to 18,000 events)
Zone number and name (21 chars)
Pipes in use (pipe 1 to 4)
Aspirator Speed & Flow control
Confirmation of filter change
Relay configuration
Referencing
Auto Learn™
Addressed Devices:
250 VESDA devices maximum
VESDA addressed Devices:
LaserPLUS Detectors & Displays
LaserSCANNER Detectors & Displays
LaserCOMPACT Detectors & Displays (VN Version Only)
LaserFOCUS with VESDAnet card Detectors & Displays
HLI (High Level Interface)
Relay modules
Remote Relays |